
Versa-Code� New Construction Quality Control Kit
Full Series of Code Inspections Form
Introduction
This form
is a checklist for defects in new construction in residential buildings. The items listed below are generally recognized as
code items for residential construction, especially one and two family dwellings. Cross-references for similar items between
different codes are referenced in brackets after the written code item.
The
International Code Council� (ICC�) and related codes (e.g. International Residential Code (IRC�), Council of American Building Officials (CABO the NFPA
was a part of this also), Uniform Building Code� (UBC�)) are indicated in the formal bracketed sections (the first
entry in the ICC sections is the IRC 2000� code section, the second entry is the 1995 CABO reference, while
the third entry is the 1997 UBC� reference).
The
National Fire Protection Association� (NFPA�) related codes are indicated in the rectangular bracketed
sections. On plumbing and mechanical issues,
the section listed applies to the Uniform Plumbing Code� and Uniform Mechanical Code�. On Electrical
issues, the section listed applies to the National Electric Code�.
The
following examples are given for further explanation:
Gas Furnace Electrical
Central furnace not on individual circuit {3603.1; 4203.1}[422-12; 422-7]
No fuse at disconnect unless thermally protected {3303.3; NA}[430-32c1, recd]
No
120V receptacle within 25 ft. on same level {3801.11;
4401.12}, [210-63*]
No
lighting switched at entry to equipment space {3803.4;
4403.3}[210-70c*]
The code
sections listed in the formal brackets --{3603.1; 4203.1}-- represent the IRC provision,
then the CABO provision respectively. If
these brackets have a third entry or listing for a code section, it is the Uniform
Building Code section, if applicable, as seen in the following line:
General
Site Requirements
Approved plans/permit not
available on site {106.3.1; 112/226.1; 196.4.2/108.2}
The code sections listed in the rectangular
brackets -- [422-12; 422-7] -- represent the 2000 UMC provision, the 97 (and then
the 94) provisions respectively. An
* with only one code provision listed means that the same code provision
applied to the earlier version(s) of the code (see above).
The following are relevant
abbreviations for the form:
- recd
recommended for any one or more of the following reasons local
practice,
accepted trade practice, recommendation to the
consumer,
etc.
- <
less than
- >
more than
- =
equal to
- cons. conservation
or energy principles
- ex. exception
- NA not
applicable
- Proh. prohibited
- psc public
service corporation or utility company
requirement/recommendation
- T
precedes a table number found in the code
- IS installation
standard from the International Association of
Plumbing
and Mechanical Officials
- AG G
appendix of the IRC
- o.c. on
center
Preliminary Stage of Inspection
General/Foundation/Site
General
Site Requirements
Approved
plans/permit not available on site {106.3.1; 112/226.1; 196.4.2/108.2}
All permits not taken
out (building, electrical, plumbing, mechanical): except fences < or = to 6 ft.,
retaining walls < or = to 4 ft., sheds, painting {105.2}
Special
inspections not identified {109.2; 306.1; 1701.3}
General Building
Issues
Approved plans & permit or
building card not on site {105.7}, [114.2]
All inspection
reports/drawings not on site {109.2; 113.1.5; 170.1}
No energy conservation
evaluation/report {1101.2}, [cons]
Retaining Walls
> 48 in. of backfill/frontfill differential expected on
retaining wall: engineering not provided {404.1.3; t404.1.1b;1609.2}
> 4 ft.
retaining wall or any size retaining wall with uphill load located above a 45� line from
bottom of retaining wall (surcharge): no permit { 105.2; NA; 1611.6}
Temporary Power
No temporary power {107.3},
Service Conductors
No white tape/ paint at ends of black insulated neutral
conductors {3307.1; 3907.1}[200-6b*]
Wire size-< #8 Cu or <
#6 Al unless only one branch circuit then branch circuit size OK {3503.2ex. 1 &2;
4102.1.3}[200-6b; 230-23b/230-31b]
No Antioxidant grease at
aluminum terminals or
Aluminum to Copper wiring
change: Non-CU/ALR connectors {3306.8; 3906.8}[110-14*/110-3b]
< 18 in. of conductor at
weatherhead {psc*}[psc*]
Inadequate guy wire/support
for temporary pole (incl. utility spec.) {3504.5; psc}[230-28; psc]
Not all 125V 15-, 20-, &
30-amp receptacles GFCI protected {NA; 4402.3}[305-6a*]
< 18 ft. above public
(streets, alleyways, etc.) or parking areas
{3504.2.2; 4104.2.2}[230-24b; psc]
< 12 ft. above residential
property/driveways {3504.2.2; 4104.2.2}[230-24b; psc]
< 10 ft. above pedestrian
traffic {3504.2.2; 4104.2.2}[230-24b; psc]
Footings Stage of Inspection (pre-pour)
Footings:
Seismic Categories D1&D2: < 3 in. clearance of rebar to soil or
< #4 (1/2 in.) vertical bar or > 4ft. on center
{403.1.3}
< #4 (1/2 in.) bar in top and bottom of footing/wall
{403.1.3.1,2; see t
404.1.b;
1806.7.1}
< 8.75 in. from soil sidewall to rebar at side in l2 in.
walls {T404.1.1(3)}
< 6.75 in. from soil sidewall to rebar at side in 10 in.
walls {T404.1.1
(4)}
< 5 in. from soil sidewall to rebar at side in 8 in. walls
{T404.1.1(2)}
Monolithic footing: < one #5 (5/8in.) or two #4 (1/2 in.)
bars in middle
third
of footing {403.1.3.2ex.}
< 12 in. overlap at splice
lap or engineered
< 20 in. if 1/2 in. rebar {recd; recd; 1912.16.1}
Bricks/etc. used instead of Adobies@ to raise rebar above soil {403.1.3;
NA; 1907.7.1}
Footings not on undisturbed
soil {403.1; Fig. 403.1a}, [NA, NA]
Wood
foundation footings: basement with < 8 in. or crawlspace with < 6 in. stone, etc.
footing
Site Slope/Grade
> 1 in 10 slope to proposed
bottom surface of footing: foundation not stepped (e.g.
to satisfy frost line requirements) {403.1.5; 401.3.1.1; 1806.4}
$1 in 3 slope near or on house lot:
Difference in elevation between flat spot/yard of uphill house
compared
with flat spot/yard of downhill house times one half, is greater
than
the distance from bottom of slope/hill to closest downhill house
wall.
{403.1.7; NA; fig.18-I-1}
Difference in elevation between flat spot/yard of uphill house
compared
with flat spot/yard of downhill house times one third, is greater
than
the distance from top of slope/hill to uphill house footing
General Site
Requirements
Top of foundation < l2 in.+
1 inch in 50 inch grade above street gutter (unless bldg. inspector approves) {403.1.7.3; 401.3; 1806.5.5}
< 3 ft. to property line
without 1 hr. construction or with openings {302.1; 302.1/302.2; t-5a}
Foundation Forms Stage of
Inspection
Foundations
Concrete Forms Issues
Unsleeved/unarched pipe
openings/pipes in forms or under footings {2603.5}; {3103.5}; {313.2}
Top, sides and end of proposed wood beam
to rest on block/concrete with < 1/2 in. air space to concrete (but can rest bottom
face of board on concrete). {323.1(4); 322.1.4; 2306.6}
Access Openings
Mechanical equipment in crawlspace: Less than 22 in. x 30
in. {1305.1.4}
No mechanical equipment in
crawlspace: Less than l8 in. x 24 in. {408.3; 409.2; 2306.3}
Vents < 3 ft. of property
line {302.2ex.2; NA; t-5a}
Vent openings not within 3 ft.
of each corner {408.1} |