
Versa-Codeä New Construction Quality Control Kit
Full Series of Code Inspections Form
Introduction
This form
is a checklist for defects in new construction in residential buildings. The items listed below are generally recognized as
code items for residential construction, especially one and two family dwellings. Cross-references for similar items between
different codes are referenced in brackets after the written code item.
The
International Code CouncilÒ (ICCÒ) and related codes (e.g. International Residential Code (IRCÒ), Council of American Building Officials (CABO the NFPA
was a part of this also), Uniform Building CodeÒ (UBCÒ)) are indicated in the formal bracketed sections (the first
entry in the ICC sections is the IRC 2000Ô code section, the second entry is the 1995 CABO reference, while
the third entry is the 1997 UBCÒ reference).
The
National Fire Protection AssociationÒ (NFPAÒ) related codes are indicated in the rectangular bracketed
sections. On plumbing and mechanical issues,
the section listed applies to the Uniform Plumbing CodeÒ and Uniform Mechanical CodeÒ. On Electrical
issues, the section listed applies to the National Electric CodeÒ.
The
following examples are given for further explanation:
Gas Furnace Electrical
Central furnace not on individual circuit {3603.1; 4203.1}[422-12; 422-7]
No fuse at disconnect unless thermally protected {3303.3; NA}[430-32c1, recd]
No
120V receptacle within 25 ft. on same level {3801.11;
4401.12}, [210-63*]
No
lighting switched at entry to equipment space {3803.4;
4403.3}[210-70c*]
The code
sections listed in the formal brackets --{3603.1; 4203.1}-- represent the IRC provision,
then the CABO provision respectively. If
these brackets have a third entry or listing for a code section, it is the Uniform
Building Code section, if applicable, as seen in the following line:
General
Site Requirements
Approved plans/permit not
available on site {106.3.1; 112/226.1; 196.4.2/108.2}
The code sections listed in the rectangular
brackets -- [422-12; 422-7] -- represent the 2000 UMC provision, the 97 (and then
the 94) provisions respectively. An
* with only one code provision listed means that the same code provision
applied to the earlier version(s) of the code (see above).
The following are relevant
abbreviations for the form:
- recd
recommended for any one or more of the following reasons local
practice,
accepted trade practice, recommendation to the
consumer,
etc.
- <
less than
- >
more than
- =
equal to
- cons. conservation
or energy principles
- ex. exception
- NA not
applicable
- Proh. prohibited
- psc public
service corporation or utility company
requirement/recommendation
- T
precedes a table number found in the code
- IS installation
standard from the International Association of
Plumbing
and Mechanical Officials
- AG G
appendix of the IRC
- o.c. on
center
Preliminary Stage of Inspection
General/Foundation/Site
General
Site Requirements
Approved
plans/permit not available on site {106.3.1; 112/226.1; 196.4.2/108.2}
All permits not taken
out (building, electrical, plumbing, mechanical): except fences < or = to 6 ft.,
retaining walls < or = to 4 ft., sheds, painting {105.2}
Special
inspections not identified {109.2; 306.1; 1701.3}
General Building
Issues
Approved plans & permit or
building card not on site {105.7}, [114.2]
All inspection
reports/drawings not on site {109.2; 113.1.5; 170.1}
No energy conservation
evaluation/report {1101.2}, [cons]
Retaining Walls
> 48 in. of backfill/frontfill differential expected on
retaining wall: engineering not provided {404.1.3; t404.1.1b;1609.2}
> 4 ft.
retaining wall or any size retaining wall with uphill load located above a 45º line from
bottom of retaining wall (surcharge): no permit { 105.2; NA; 1611.6}
Temporary Power
No temporary power {107.3},
Service Conductors
No white tape/ paint at ends of black insulated neutral
conductors {3307.1; 3907.1}[200-6b*]
Wire size-< #8 Cu or <
#6 Al unless only one branch circuit then branch circuit size OK {3503.2ex. 1 &2;
4102.1.3}[200-6b; 230-23b/230-31b]
No Antioxidant grease at
aluminum terminals or
Aluminum to Copper wiring
change: Non-CU/ALR connectors {3306.8; 3906.8}[110-14*/110-3b]
< 18 in. of conductor at
weatherhead {psc*}[psc*]
Inadequate guy wire/support
for temporary pole (incl. utility spec.) {3504.5; psc}[230-28; psc]
Not all 125V 15-, 20-, &
30-amp receptacles GFCI protected {NA; 4402.3}[305-6a*]
< 18 ft. above public
(streets, alleyways, etc.) or parking areas
{3504.2.2; 4104.2.2}[230-24b; psc]
< 12 ft. above residential
property/driveways {3504.2.2; 4104.2.2}[230-24b; psc]
< 10 ft. above pedestrian
traffic {3504.2.2; 4104.2.2}[230-24b; psc]
Footings Stage of Inspection (pre-pour)
Footings:
Seismic Categories D1&D2: < 3 in. clearance of rebar to soil or
< #4 (1/2 in.) vertical bar or > 4ft. on center
{403.1.3}
< #4 (1/2 in.) bar in top and bottom of footing/wall
{403.1.3.1,2; see t
404.1.b;
1806.7.1}
< 8.75 in. from soil sidewall to rebar at side in l2 in.
walls {T404.1.1(3)}
< 6.75 in. from soil sidewall to rebar at side in 10 in.
walls {T404.1.1
(4)}
< 5 in. from soil sidewall to rebar at side in 8 in. walls
{T404.1.1(2)}
Monolithic footing: < one #5 (5/8in.) or two #4 (1/2 in.)
bars in middle
third
of footing {403.1.3.2ex.}
< 12 in. overlap at splice
lap or engineered
< 20 in. if 1/2 in. rebar {recd; recd; 1912.16.1}
Bricks/etc. used instead of Adobies@ to raise rebar above soil {403.1.3;
NA; 1907.7.1}
Footings not on undisturbed
soil {403.1; Fig. 403.1a}, [NA, NA]
Wood
foundation footings: basement with < 8 in. or crawlspace with < 6 in. stone, etc.
footing
Site Slope/Grade
> 1 in 10 slope to proposed
bottom surface of footing: foundation not stepped (e.g.
to satisfy frost line requirements) {403.1.5; 401.3.1.1; 1806.4}
$1 in 3 slope near or on house lot:
Difference in elevation between flat spot/yard of uphill house
compared
with flat spot/yard of downhill house times one half, is greater
than
the distance from bottom of slope/hill to closest downhill house
wall.
{403.1.7; NA; fig.18-I-1}
Difference in elevation between flat spot/yard of uphill house
compared
with flat spot/yard of downhill house times one third, is greater
than
the distance from top of slope/hill to uphill house footing
General Site
Requirements
Top of foundation < l2 in.+
1 inch in 50 inch grade above street gutter (unless bldg. inspector approves) {403.1.7.3; 401.3; 1806.5.5}
< 3 ft. to property line
without 1 hr. construction or with openings {302.1; 302.1/302.2; t-5a}
Foundation Forms Stage of
Inspection
Foundations
Concrete Forms Issues
Unsleeved/unarched pipe
openings/pipes in forms or under footings {2603.5}; {3103.5}; {313.2}
Top, sides and end of proposed wood beam
to rest on block/concrete with < 1/2 in. air space to concrete (but can rest bottom
face of board on concrete). {323.1(4); 322.1.4; 2306.6}
Access Openings
Mechanical equipment in crawlspace: Less than 22 in. x 30
in. {1305.1.4}
No mechanical equipment in
crawlspace: Less than l8 in. x 24 in. {408.3; 409.2; 2306.3}
Vents < 3 ft. of property
line {302.2ex.2; NA; t-5a}
Vent openings not within 3 ft.
of each corner {408.1} |